Short answer: A server room or comms cupboard needs its own air conditioning, separate from the office system, because the equipment makes heat all day, every day, including winter weekends when office cooling is off. Size it for the equipment's heat output with room to grow, choose a unit rated for year round cooling, and plan for a fault.
Why comms rooms are different
A London office might need cooling from May to September, during working hours. A server room or comms cupboard needs it every hour of every day. Network switches, servers, storage and power supplies turn almost all the electricity they use into heat, and they do it constantly. In a small, closed cupboard that heat builds fast.
The usual problems are:
- the comms cupboard sharing the office system, which switches off at 7pm
- a unit that heats in winter because the office system is set to heat
- a cupboard with no cooling at all, just a door left open
- a unit sized years ago, before more equipment was added
Sizing it properly
Equipment heat output is the starting point. As a rule of thumb, the heat given off is close to the electrical power the equipment draws. Add to that:
- lighting
- any people working in the room
- heat gain through walls, especially an outside wall or a wall next to a kitchen
- sun on any windows
Then allow room for growth. Comms rooms rarely get smaller.
| Factor | Why it matters |
|---|---|
| Equipment power draw | the main heat source, running all the time |
| Room size and walls | small rooms heat up faster |
| Outside walls or windows | add heat in summer |
| Future equipment | avoid undersizing in two years |
| Target temperature | follow the equipment makers’ guidance |
Choosing a unit for year round cooling
Home split systems are designed mostly for summer cooling. A comms room needs cooling in January too, when the outdoor temperature is low. Not every unit is happy cooling when it is cold outside. Choose a unit the manufacturer rates for low ambient cooling, so it keeps working through a London winter.
Other features worth having:
- auto restart after a power cut, so cooling resumes without anyone pressing a button
- a high temperature alarm or a link to your building management or monitoring system
- dedicated controls that office staff cannot change by accident
Resilience
If a business depends on its comms room, a single unit is a single point of failure. Common approaches are:
- two units with a controller that runs one as duty and one as standby, swapping over regularly
- a temperature alarm that alerts someone if the room gets too warm
- a service plan with visits more frequent than for office cooling, since the unit runs constantly
Condensate and leaks
A unit running all year makes condensate for much of it. Water and IT equipment do not mix, so the condensate route matters more here than anywhere. Avoid mounting the indoor unit directly above racks if you can. If the drain relies on a pump, consider a pump with an alarm or a cut out that stops the unit if water backs up. Our guide to air conditioning leaking water explains the common causes.
Landlord and building rules
In the City of London, most offices are let floor by floor, and the outdoor unit for a comms room usually has to go on a roof plant deck, a terrace or a designated plant area controlled by the landlord. Expect to need a licence for alterations and the landlord’s agreement on the outdoor unit location, pipe routes through risers and the condensate connection. Some buildings provide a dedicated cooling supply for tenant comms rooms, which can be simpler. Our City of London page explains how City buildings handle this.
New outdoor plant on commercial property normally needs planning permission, because the heat pump permitted development rules apply to homes only (Planning Portal).
Legal checks
The refrigerant work must be done by an engineer with an F-gas qualification, working for a company certified by an approved body listed on gov.uk. If the comms room units and the office system together exceed 12kW, the building needs a TM44 inspection at least every five years, explained in our TM44 guide. Larger systems may also need F-gas leak checks.
Getting it right
The steps are straightforward: measure the load, choose a unit built for constant cooling, plan the drain, add an alarm and keep it serviced. Our office air conditioning page explains how a commercial survey and install run.
Questions to ask before you install
Before choosing a system for a comms room, it helps to answer:
| Question | Why it matters |
|---|---|
| What is the total power draw of the equipment? | sets the cooling load |
| Will more equipment be added in the next few years? | avoids undersizing |
| Is there an outside wall or window? | adds heat in summer |
| Where can the outdoor unit go, and who controls that space? | landlord consent and planning |
| Where will condensate drain? | water near IT equipment is a risk |
| Who gets alerted if the room overheats? | a fault at the weekend can go unnoticed |
| Is a standby unit justified? | depends on what the business can tolerate |
The answers shape the design and the quote, and they are what the landlord’s engineer will want to see too.
Quick questions
Can I use the office air conditioning for the server room?
It is not a good idea. Office systems are often switched off at night and weekends, and in winter they may be heating. A comms room needs cooling all the time, so it should have its own unit.
How do I size air conditioning for a server room?
Start with the heat output of the equipment, which is close to the electrical power it uses, then add heat from lighting, people and any sun on walls or windows. Allow headroom for more equipment later.
What happens if the server room air conditioning fails?
Temperatures can rise quickly in a small room. Many businesses add a second unit or a high temperature alarm so a fault is noticed and covered.
Last updated 23 October 2026. Written for homes in London. Rules can change, so check the linked sources for the latest position.